Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.5.2.4.3
AI4 Signal Range
0
1
0
154
See P3.5.2.1.3.
P3.5.2.4.4
AI4 Custom. Min
-160.00
160.00
%
0.00
155
See P3.5.2.1.4.
P3.5.2.4.5
AI4 Custom. Max
-160.00
160.00
%
100.00
156
See P3.5.2.1.5.
P3.5.2.4.6
AI4 Signal Inversion
0
1
0
162
See P3.5.2.1.6.
Table 49: Analog Input 5 Settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.5.2.5.1
AI5 Signal Selection
AnIN SlotE.1
188
See P3.5.2.1.1.
P3.5.2.5.2
AI5 Signal Filter Time
0.00
300.00
s
0.1
189
See P3.5.2.1.2.
P3.5.2.5.3
AI5 Signal Range
0
1
0
190
See P3.5.2.1.3.
P3.5.2.5.4
AI5 Custom. Min
-160.00
160.00
%
0.00
191
See P3.5.2.1.4.
P3.5.2.5.5
AI5 Custom. Max
-160.00
160.00
%
100.00
192
See P3.5.2.1.5.
P3.5.2.5.6
AI5 Signal Inversion
0
1
0
198
See P3.5.2.1.6.
Table 50: Analog Input 6 Settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.5.2.6.1
AI6 Signal Selection
AnIN SlotE.2
199
See P3.5.2.1.1.
P3.5.2.6.2
AI6 Signal Filter Time
0.00
300.00
s
0.1
200
See P3.5.2.1.2.
P3.5.2.6.3
AI6 Signal Range
0
1
0
201
See P3.5.2.1.3.
P3.5.2.6.4
AI6 Custom. Min
-160.00
160.00
%
0.00
203
See P3.5.2.1.4.
P3.5.2.6.5
AI6 Custom. Max
-160.00
160.00
%
100.00
204
See P3.5.2.1.5.
P3.5.2.6.6
AI6 Signal Inversion
0
1
0
209
See P3.5.2.1.6.
Table 51: Digital Output Settings on Standard I/O Board, Slot B
Index
Parameter
Min
Max
Unit
De-
fault
ID
Description
P3.5.3.2.1
RO1 Func-
tion
0
75
Varies
11001
The function selection for R01:
0 = None
1 = Ready
2 = Run
3 = General fault
4 = General fault inverted
5 = General alarm
6 = Reversed
AB298035655957en-000201 / DPD01083 | 99Danfoss A/S © 2023.08
Parameters Menu
VACON® 100 FLOW
Application Guide