FC 202 N500 N560
Typical shaft output at 460 V [hp] 600 650 650 750
Typical shaft output at 480 V [kW] 530 560 560 630
Enclosure size E6h E6h
Output current (3-phase)
Continuous (at 400 V) [A] 800 880 880 990
Intermittent (60 s overload) (at 400 V) [A] 1200 968 1320 1089
Continuous (at 460/480 V) [A] 730 780 780 890
Intermittent (60 s overload) (at 460/480 V) [A] 1095 858 1170 979
Continuous kVA (at 400 V) [kVA] 554 610 610 686
Continuous kVA (at 460 V) [kVA] 582 621 621 709
Continuous kVA (at 480 V) [kVA] 632 675 675 771
Maximum input current
Continuous (at 400 V) [A] 771 848 848 954
Continuous (at 460/480 V) [A] 704 752 752 858
Maximum number and size of cables per phase
- Mains [mm
2
(AWG)]
4x185 (4x350 mcm) 4x185 (4x350 mcm)
- Mains with disconnect [mm
2
(AWG)]
4x185 (4x350 mcm) 4x185 (4x350 mcm)
- Mains with fusible disconnect [mm
2
(AWG)]
4x185 (4x350 mcm) 4x185 (4x350 mcm)
- Mains with contactor [mm
2
(AWG)]
4x185 (4x350 mcm) 4x185 (4x350 mcm)
- Motor [mm
2
(AWG)]
4x185 (4x350 mcm) 4x185 (4x350 mcm)
Drive module power loss at 400 V [W]
(1) (2) (3)
8352 9473 9449 11102
Estimated power loss at 460 V [W]
(1) (2) (3)
7182 7809 7771 9236
Drive efficiency
(2)
0.98 0.98
Output frequency [Hz]
(4)
0–590 0–590
Heat sink overtemperature trip [°C (°F)] 110 (230) 100 (212)
Control card overtemperature trip [°C (°F)] 80 (176) 80 (176)
PHF overtemperature trip [°C (°F)] 150 (302) 150 (302)
dU/dt filter overtemperature trip [°C (°F)] 150 (302) 150 (302)
Sine-wave filter overtemperature trip [°C (°F)] 150 (302) 150 (302)
1
Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions.) These values are based on a typical motor
efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies to dimensioning of drive cooling. If the switching frequency is higher than the default
setting, the power losses can increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/
knowledge-center/energy-efficiency-directive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B
each add only 4 W.
2
Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy efficiency class, see the Ambient Conditions
section. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
Specifications
Operating Guide | VLT® AQUA Drive FC 202
AQ262141056213en-000101 / 130R0882
164 | Danfoss A/S © 2018.10