Revision 2016/03, 6ELE, V1.14
4-97
Parameter
Function Setting
Factory
Setting
End
user’s
master
End
user’s
slave
Note
10.21
Restart Delay
Time after
Erroneous PID
Deviation Level
1 to 9999 sec 60 1800 1800
10.22
Set Point
Deviation Level
0 to 100% 0 5 5
When the
feedback
value and
the target
value are
both 0.15kg
(3kg*5%
=0.15kg)
which
means
when
feedback
value is
more than
2.85kg and
time
exceeds 10
seconds,
the inverter
starts to
decelerate
then stop.
The
deceleration
time here
follows the
setting at
Pr01.12
Deceleration
Time 2.
When
feedback
value is
under
2.85Kg, the
inverter
starts to run.
10.23
Detection Time of
Set Point
Deviation Level
0 to 9999 sec 10 10 10