User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
Chapter 3. Commands Page 3-39
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
BATTERY TIMER CSV
Description: Displays the battery discharge history in a comma separated value format.
Command Level: 6
Syntax: BATTERY TIMER CSV
BA TI CS
Comments: none
Notes: none
Related Commands: BATTERY TIMER CLR, BATTERY TIMER SET, BATTERY
TIMER STATUS
Example:
Command<6>: BATTERY TIMER CSV
Discharge #,Duration, AC Fail Time, AC Fail Date, Lowest Voltage, Avg. Current
D01,00:00,09:20,02/26/03, 27.00, 88.00,
D02,00:07,09:12,02/26/03, 27.00, 88.00,
D50,00:07,15:12,02/14/03, 27.00, 88.00,