Section 5847 User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Page 3-372 Chapter 3. Commands
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
REPORT ALARM ENVIRONMENT
(REPT ALM ENV)
Referenced In: TR-NWT-000833, Issue 5; pg. 5-13
General Description: Generated by an LMS1000 to report the occurrence of
environmental alarms.
Related Commands: RETRIEVE-ALARM ENVIRONMENT
Related Messages: None
LMS1000 Equivalent: None
LMS1000 Message Format Variations:
<ntfcncde>
This is the notification code parameter associated with the environmental alarm
conditions being reported.
Valid values for this parameter are as follows:
CR critical alarm
MJ major alarm
MN minor alarm
CL cleared alarm
Values are derived from the NOTIFICATION CODE attribute of the LMS1000 channel or
limit configuration with which the alarm condition is associated. Parameter grouping
cannot be used with this parameter.
<almtype>
This is the alarm type parameter of environmental alarm(s) to be reported. Values are
derived from the CONDITION TYPE attribute of the LMS1000 channel or limit
configuration with which the alarm condition is associated. Parameter grouping cannot
be used with this parameter.
<ocrdat>
This is the date when the triggering event occurred (i.e., the threshold was crossed). The
format for this parameter is MOY-DOM (Month-Of-Year - Day-Of-Month). MOY ranges
from 1 to 12, and DOM ranges from 1 to 31. A NULL value for this parameter defaults to
the date in the message header. Parameter grouping cannot be used with this
parameter.
<ocrtm>
This is the time when the triggering event occurred. The format for this parameter is
HOD-MOH-SOM (Hour-Of-Day - Minute-Of-Hour - Second-Of-Minute). HOD ranges from
0 to 23. MOH and SOM range from 0 to 59. A NULL value for this parameter defaults to
the time in the message header. Parameter grouping cannot be used with this
parameter.