User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
Chapter 3. Commands Page 3-191
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SET LPS SYSTEM HI2TEMPALM
Description: Sets the LPS "high temperature 2 alarm" value.
Command Level: 5
Syntax: SET LPS SYSTEM HI2TEMPALM
SE LP SY HI2
Comments: The current value is displayed, followed by a prompt to enter a new value.
Notes: The following message is displayed if the setting was not accepted by the MCA.
Not Changed!
Related Commands: none
Example:
Command<6>: set lps sys hi2
High Temperature #2 Alarm: 100 DegC
High Temperature #2 Alarm: 101
High Temperature #2 Alarm NOT CHANGED!
___________________________________________________________________________________
Command<6>: set lps sys hi2
High Temperature #2 Alarm: 100 DegC
High Temperature #2 Alarm: 99
New High Temperature #2 Alarm Accepted.