SET LPS SYSTEM LOADACURRENT
Description: Sets the LPS "Load Group A current alarm" value.
Command Level: 5
Syntax: SET LPS SYSTEM LOADACURRENT
SE LP SY LOADA
Comments: The current value is displayed, followed by a prompt to enter a new value.
Notes: The following message is displayed if the setting was not accepted by the MCA.
Not Changed!
Related Commands: none
Example:
Command<6>: set lps sys loada
A Load Overcurrent Alarm: 2500 Amps
A Load Overcurrent Alarm: 2600
New A Load Overcurrent Alarm Accepted.