Section 5847 User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Page 3-154 Chapter 3. Commands
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SET AID
Description: This command is only available if the TL1 software option is installed in the
system. Configures up to thirty-two access identifiers, and associates sub-access
identifiers to the access identifiers.
Command Level: 6
Syntax: SET AID [n]
SE AI [n]
Comments: To add or delete channels, type D at the prompt to display a complete list of
channels previously linked to the current access identifier. The channel number,
previously configured channel name, and previously configured channel sub-access
identifier are displayed.
Type the number(s) of all channels to be added or removed. Channels can be specified
by entering a single channel number (e.g. A0001, B0008), or by entering a range of
channel numbers (e.g. A0001-8, L0001-L0012).
Notes: The terms Access Identifier, LMS1000 Access Identifier, and LMS1000 Sub-
Access Identifier are described as follows.
Access Identifier:
In an NMA system, a unique access identifier (AID) is used to identify
each entity contained within the system. LMS1000 must be configured to allow a single
access identifier to be used to access and report on an NMA system entity which may
consist of a multiple of sub-entities, each monitored by a variety of LMS1000 channels.
This is accomplished by configuring LMS1000 access identifiers and LMS1000 sub-
access identifiers as described next. A list of access identifiers and sub-access
identifiers appears in TA-NWT-001360, Table 4-1.
LMS1000 can be set to use an "AID delimiter". When enabled, LMS1000 access
identifier field and LMS1000 sub-access identifier field in all responses to TL1 commands
and reports containing a TL1 access identifier field is separated by a hyphen. The use of
an "AID delimiter" (a hyphen) can be enabled or disabled, as described under LMS1000
Command SET MODE.
LMS1000 Access Identifier:
Thirty-two (32) LMS1000 access identifiers are available.
LMS1000 access identifier is used to uniquely identify a system entity (such as a power
plant).
LMS1000 Sub-Access Identifier:
LMS1000 sub-access identifiers are used to uniquely
identify each sub-entity of an entity (such as each rectifier, each battery string, etc.
contained in the power plant).
The association between all LMS1000 channels monitoring an individual rectifier, an
individual battery string, etc. is made by configuring each channel monitoring this
individual sub-entity with a unique sub-access identifier name. This is done when the
individual LMS1000 channels are configured.
Thus all LMS1000 channels monitoring "rectifier one" may be configured with the sub-
access identifier name RECT1. All LMS1000 channels monitoring "rectifier two" may be
configured with sub-access identifier RECT2. All LMS1000 channels monitoring "battery
string one" may be configured with the sub-access identifier BATSTR1. All LMS1000