User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
Chapter 3. Commands Page 3-157
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SET CHANNELS
Description: Allows channels to be added to or deleted from the configuration of the
currently logged on user.
Command Level: 6
Syntax: SET CHANNELS
SE CH
Comments: Information presented includes the type of channel (analog, binary,
function, group, relay, LED, or energy management) and the user description of the
channel. If the channel is configured to be inactive, "not active" will also be displayed.
After this information is presented, the user can add or delete channels as required.
When in the edit mode (either adding or deleting channels) the user can enter the
character D to display the present list of channels. To facilitate editing, a sequence of
channels can be entered, such as B0001-0064. In this example binary channels 1
through 64 in the Master Node would be added or deleted, dependent upon the operation
being performed.
Notes: none
Related Commands: CHANNELS
Example:
Command<6>: SET CHANNELS
USER NO. 6 CHANNELS:
A0001 Analog Channel 1
A0002 Analog Channel 2
A0004 Analog Channel 4
A0033 Analog Channel 33
A0034 Analog Channel 34 not active
A0037 Analog Channel 37 not active
A0038 Analog Channel 38 not active
A0039 Analog Channel 39 not active
A0040 Analog Channel 40
END OF USER NO. 6 CHANNELS
Enter channel (eg. A0012 or A0001-0006) or D to display.
Add Channel: A0013
Channel does not exist!
Add Channel: A0064
Add Channel:
Enter channel (eg. A0012 or A0001-0006) or D to display.
Del Channel: A0064
Del Channel: