Section 5847 User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Page 3-94 Chapter 3. Commands
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
LIMITS
Description: Displays the alarm limits for each analog and function input.
Command Level: 2
Syntax: LIMITS[node_designator] [channel_range] [node_range]
LIMITS A[[node_number] channel_number]
LIMITS F[channel_number]
LIM[node_designator] [channel_range] [node_range]
LIM A[[node_number] channel_number]
LIM F[channel_number]
Comments: Typing a command like PRCONFIG A1 will list the entire channel
configuration for analog channel 1 including the limits.
Notes: When using channel_range, only channel types A or F are valid. Except for LPS
distribution points, LPS analog channels cannot be configured to alarm because those
limits are controlled by the MCA and result in binary alarms in the LMS.
Related Commands: none
Example:
Command<2>: LIMITS A
ANALOG CHANNEL ALARM LIMITS AS OF 07:36:02 ON 01/01/01.
Chan Description
A0001 Analog Channel 1
Limit / Name Class Condtype Ntfc Svef
70.0 H HVA2 MAJOR TOOHIGH MJ SA
Condition Description
THIS VOLTAGE IS TOO HIGH
60.0 H HVA1 MAJOR HIGH MJ SA
Condition Description
THIS VOLTAGE IS HIGH
50.0 L LVA1 MINOR LOW MN NSA
Condition Description
THIS VOLTAGE IS LOW
40.0 L LVA2 MINOR TOOLOW MN NSA
Condition Description
THIS VOLTAGE IS TOO LOW
A0002 Analog Channel 2
Limit / Name Class Condtype Ntfc Svef
7000 H ABOVE 7000 MAJOR TOOHIGH MJ SA
Condition Description
THIS CURRENT IS ABOVE 7000 AMPS
6000 H ABOVE 6000 MAJOR HIGH MJ SA
Condition Description
THIS CURRENT IS ABOVE 6000 AMPS
500 L BELOW 500 MINOR LOW MN NSA
Condition Description
THIS CURRENT IS BELOW 500 AMPS
100 L BELOW 100 MINOR TOOLOW MN NSA
Condition Description
THIS CURRENT IS BELOW 100 AMPS