User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
Chapter 3. Commands Page 3-95
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Command<6>: LIMITS F
FUNCTION CHANNEL ALARM LIMITS AS OF 07:41:17 ON 02/09/96.
Chan Description
F0001 Function Channel 1
Limit / Name Class Condtype Ntfc Svef
5000.H ABOVE 5000 TOOHIGH CR SA
Condition Description
CURRENT IS ABOVE 5000 AMPS
500.0L BELOW 500 HIGH CR SA
Condition Description
CURRENT IS BELOW 500 AMPS
None
None
F0002 Function Channel 2
Limit / Name Class Condtype Ntfc Svef
70.00H HVA2 MAJOR TOOHIGH MJ SA
Condition Description
VOLTAGE IS ABOVE 70 VOLTS
60.00LH HVA1 MAJOR HIGH MJ SA
Condition Description
VOLTAGE IS ABOVE 60 VOLTS
50.00L LVA1 MINOR LOW MJ SA
Condition Description
VOLTAGE IS BELOW 50 VOLTS
40.00L LVA2 MINOR TOOLOW MJ SA
Condition Description
VOLTAGE IS BELOW 40 VOLTS