RETRIEVE-LOG
(RTRV-LOG)
Referenced In: TA-NWT-000200, Issue 5; pg. 242
General Description: Instructs LMS1000 to retrieve the contents of an existing log.
Related Commands: None
LMS1000 Access Level: 1
LMS1000 Equivalent: LOG, HSTRY, EVENTS
LMS1000 Input Format Variations:
<aid>
The access identifier (<aid>) parameter does not apply. The only valid value for this
parameter is NULL. Invalid values received for this parameter return an error response
with the error code IIAC.
<lognm>
This is the name of the log.
Valid values for this parameter are the following text strings.
ALARM specifies the retrieval of the LMS1000s alarm log
HSTRY specifies retrieval of the predetermined number of alarm log entries
specified by the LMS1000s mechanized interface configuration
ACTIV specifies the retrieval of the LMS1000s event log
Invalid values for this parameter return an error response with the error code IDNV.
LMS1000 Response Format Variations:
<lognm>
This is the name of the log. Valid values are the same as for the input format.