SET VORTEX SYSTEM TSTEQVOLT
Description: Sets the VPS "test/equalize output voltage" value.
Command Level: 6
Syntax: SET VORTEX SYSTEM TSTEQVOLT
SE V SY TSTEQVOLT
Comments: The current value is displayed, followed by a prompt to enter a new value.
Notes: The MCA does not allow an adjustment which could result in a service
interruption. Refer to the VPS instruction manual's test/equalize adjustment procedure
for details.
The following message is displayed if the setting was not accepted by the MCA.
Invalid value entered, request to update setting denied.
Related Commands: none
Example:
Command<6>: SET V SYSTEM TSTEQVOLT
Test/Equalize Voltage: 53.00 VDC
Test/Equalize Voltage: