User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
Chapter 3. Commands Page 3-121
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
POWER
Description: Displays power consumption data for function channels configured to
calculate power
Command Level: 1
Syntax: POWER
PO
POWER CSV
PO CSV
Comments: Power consumption data is generated and stored for function channels
configured with the UNIT TEXT of KW, and the appropriate program line to multiply the
value of the analog channel monitoring system voltage times the value of the analog
channel monitoring load current, then divide this product by 1000 (or multiple it by 0.001).
Power consumption data consists of power consumed for current day, current week, and
current month. In addition, power consumption data for the previous day, previous week,
and previous month is also stored and displayed.
Entering the command modifier CSV displays the power consumption report in the
"comma separated value" format. This allows the data to be imported into a
spreadsheet.
Notes: Available only if the Power Metering software option is installed.
Related Commands: CLR POWER
Example:
Command<1>: POWER
POWER CONSUMPTION STATISTICS AS OF 13:04:45 ON 01/01/01
F0001 POWER STATS: LOADA POWER
Daily
04/28/98: 55.07 KWH
04/29/98: 29.80 KWH
Weekly
04/19/98 THROUGH 04/25/98: 384.8 KWH
04/26/98 THROUGH 04/29/98: 194.9 KWH
Monthly
03/14/98 THROUGH 03/31/98: 887.9 KWH
04/01/98 THROUGH 04/29/98: 1505.0 KWH
F0002 POWER STATS: BDFB POWER
Daily
04/28/98: 109.20 KWH
04/29/98: 59.17 KWH
Weekly
04/19/98 THROUGH 04/25/98: 762.8 KWH
04/26/98 THROUGH 04/29/98: 386.8 KWH
Monthly
03/14/98 THROUGH 03/31/98: 1868.0 KWH
04/01/98 THROUGH 04/29/98: 3098.0 KWH
F0003 POWER STATS: LOADB POWER
Daily
04/28/98: 147.40 KWH
04/29/98: 79.85 KWH

Table of Contents