User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
Chapter 3. Commands Page 3-333
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
OPERATE-EXTERNAL-CONTROL
(OPR-EXT-CONT)
Referenced In: TR-NWT-000833, Issue 5; pg. 4-153
General Description: Instructs LMS1000 to activate a specified relay channel to
operate an external control.
Momentary operation of the external control is not implemented in LMS1000.
An entry is made in the LMS1000’s event log indicating this command was executed by
the current sessions user.
Related Commands: RELEASE-EXTERNAL-CONTROL, RETRIEVE-EXTERNAL-
CONTROL
LMS1000 Access Level: 5
An error response with the error code PICC is returned if this command is entered by a
valid user whose level of access is less than the access level of this command.
LMS1000 Equivalent: SET RLY
LMS1000 Input Format Variations:
<aid>
Specifying a value of ALL for the access identifier (<aid>) parameter requests the
activation of all LMS1000 relay channels specified by the control type (<conttype>)
parameter. A NULL value is not permitted for this parameter. Invalid values received for
this parameter return an error response with the error code IIAC.
<conttype>
The control type (<conttype>) parameter is an attribute of the LMS1000 relay channel
configuration. A NULL value requests activation of all LMS1000 relay channels identified
by the access identifier (<aid>) parameter. When the access identifier (<aid>) parameter
is ALL, the control type (<conttype>) parameter should not be NULL. Invalid values
received for this parameter return an error response with the error code IDNV.
<dur>
This is the duration for which the external control is to be operated. Parameter grouping
cannot be used with this parameter.
Valid values for the <dur> parameter are as follows:
CONTSContinuous
LMS1000 does not support the value of MNTRY for this parameter. If the value MNTRY
is received, an error response with the error code INUP is returned. Other invalid values
received for this parameter return an error response with the error code IDNV. A NULL
value for this parameter is not allowed. If a NULL value is received for this parameter, an
error response with the error code IDNV is returned.