RETRIEVE-ATTRIBUTE-ENVIRONMENT
(RTRV-ATTR-ENV)
Referenced In: TR-NWT-000833, Issue 5; pg. 4-237
General Description: Instructs LMS1000 to send the current attributes associated with
the specified environmental alarm.
Related Commands: SET-ATTRIBUTE-ENVIRONMENT
LMS1000 Access Level: 2
An error response with the error code PICC is returned if this command is entered by a
valid user whose level of access is less than the access level of this command.
LMS1000 Equivalent: None
LMS1000 Input Format Variations:
<aid>
The access identifier (<aid>) parameter identifies equipment associated with the
environmental alarm being requested. Entering a value of ALL requests retrieval of all
environmental alarms specified by the notification code (<ntfcncde>) parameter and
alarm type (<almtype>) parameter. A NULL value is not permitted for this parameter.
Invalid values received for this parameter return an error response with the error code
IIAC.
<ntfcncde>
Specifies the notification code parameter associated with the environmental alarm
conditions being retrieved. This parameter is an attribute of the LMS1000 channel or limit
configuration.
Valid values for this parameter are as follows:
CR critical alarm
MJ major alarm
MN minor alarm
NULL request retrieval of attributes for environmental alarms for all of the above
codes
Invalid values for this parameter return an error response with the error code IDNV.
<almtype>
Specifies the alarm type parameter associated with the environmental alarms being
retrieved. Specifying a NULL value requests retrieval of all types of environmental
alarms. Values are derived from the CONDITION TYPE attribute of the LMS1000
channel or limit configuration with which the alarm is associated. The error code for an
invalid value for this parameter is IDNV.