User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
Chapter 3. Commands Page 3-337
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
RETRIEVE-ALARM
(RTRV-ALM-{EQPT|ALL})
Referenced In: TR-NWT-000833, Issue 5; pg. 4-205
General Description: Instructs LMS1000 to send the current state of its alarm
conditions associated with one or more equipment units, facilities, etc. within LMS1000.
Related Commands: None
Related Messages: REPORT ALARM EQUIPMENT
LMS1000 Access Level: 1
LMS1000 Equivalent: ALARMS <t<n>>
LMS1000 Input Format Variations: The command code modifier COM is not
supported.
<aid>
Specifying a value of ALL for the access identifier (<aid>) parameter requests retrieval of
alarm conditions for all access identifiers of the type defined by the command code
modifier. Use of the command code modifier ALL results in retrieval of all alarm
conditions in LMS1000. If the command code modifier is ALL, the value of the access
identifier must be ALL. A NULL value is not permitted for this parameter. Invalid values
received for this parameter return an error response with the error code IIAC.
<ntfcncde>
Specifies the notification code parameter associated with the alarm conditions being
retrieved. This parameter is an attribute of the LMS1000 channel or limit configuration.
Valid values for this parameter are as follows:
CR critical alarm
MJ major alarm
MN minor alarm
NULL request retrieval of alarm conditions for all of the above codes
Invalid values for this parameter return an error response with the error code IDNV.
<condtype>
Specifies the condition type parameter of alarm conditions to be retrieved. A NULL value
causes all conditions classified as alarm conditions to be retrieved. This parameter is
an attribute of the LMS1000 channel or limit configuration. Invalid values for this
parameter return an error response with the error code IDNV.
<srveff>
Specifies the service effect parameter caused by the alarm conditions to be retrieved.
This parameter is an attribute of the LMS1000 channel or limit configuration.