SET LPS SYSTEM TSTEQMODE
Description: Sets the LPS to the float or test/equalize mode.
Command Level: 6
Syntax: SET LPS SYSTEM TSTEQMODE
SE LP SY TSTEQM
Comments: The current operating mode is displayed, followed by a prompt to change
the operating mode.
Notes: None
Related Commands: none
Example:
Command<6>: set lps sys tsteqm
System is in float mode.
Turn test equalize mode ON or OFF? on
Test equalize mode is ON
___________________________________________________________________________________
Command<6>: set lps sys tsteqm
System is in test equalize mode.
Turn test equalize mode ON or OFF? off
Test equalize mode is OFF
___________________________________________________________________________________
Command<6>: set lps sys tsteqm on
System is in float mode.
Turn test equalize mode ON or OFF? on
Test equalize mode is ON