User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
Chapter 3. Commands Page 3-365
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
This is the desired threshold level to be set for the monitor type parameter specified.
Valid data types for the threshold level parameter for a given monitor type parameter are
the same as for the corresponding monitor type parameter (e.g., for the channel with
which the threshold is associated). This parameter is required in the input.
<locn>
This is the location of the threshold being set. This parameter specifies the threshold
number (alarm limit number) of the specified analog or function channel. Valid values for
this parameter are LINE-x, where x is a positive integer from one through four, which
specifies the threshold number of the channel with which the threshold is associated.
This parameter is required in the input. Invalid values received for this parameter return
an error response with the error code IDNV.
<dirn>
This parameter does not apply to LMS1000. The only valid value for this parameter is
NULL. Invalid values received for this parameter return an error response with the error
code IDNV.
<tmper>
This parameter does not apply to LMS1000. The only valid value for this parameter is
NULL. Invalid values received for this parameter return an error response with the error
code IDNV.
LMS1000 Response Format Variations: None