USER RESTART MANUAL (max. number = 16, including USER RESTART MONITORED)
Using the USER RESTART MANUAL op-
erator the restart signal is saved as
per the following truth table.
Clear
Restart
I
N
Q
1
X
X
0
X
X
0
0
0
L
1
Retain
memory
0
Rising edge
1
1
0
Falling edge
1
Retain
memory
Parameters
Enable Clear: If selected, the memory process can be reset.
USER RESTART MONITORED (max. number = 16, including USER RESTART MANUAL)
Using the USER RESTART MONITORED
operator the restart signal is saved as per
the following truth table.
Clear
Restart
I
N
Q
1
X
X
0
X
X
0
0
0
L
1
Retain
memory
0
Rising edge
1
Retain
memory
0
1
1
Parameters
Enable Clear: If selected, the memory process can be reset.