Password protection
To upload and save the project, you must enter a password in EUCHNER Safety Designer.
The default password must be changed to prevent tampering (password level 2) or
so that the configuration loaded in MSC is not visible (password level 1).
Password level 1
All operators who use the system MSC-CB must have a level 1 PASSWORD.
Using this password it is only possible to display the LOG file, the layout of the system,
the real-time MONITOR and upload processes.
On the initialization of the system for the first time the operator must use the password ""
(ENTER key).
System planers who know the level 2 password can assign a new password for level 1 (al-
phanumeric, max. 8 characters).
Operators who know this password are authorized to upload the project (from MSC-
CB to PC), to edit or to save it.
Password level 2
System planers who are authorized to work on the preparation of the project must know
the level 2 PASSWORD. On the initialization of the system for the first time the operator
must use the password "SAFEPASS" (upper case).
System planers who know the level 2 password can assign a new password for level 2 (al-
phanumeric, max. 8 characters).
Using this password the project can be uploaded (from PC to MSC-CB), edited and
saved. In other words, complete control of the PC => MSC system is possible using
this password.
On UPLOADING a new project, you can change the level 2 password.
Should one of these passwords no longer be available, please contact EUCHNER to
request an unlock file (if the unlock file is saved in the correct folder, the button
appears on the toolbar). Press the button to reset the level 1 and 2 passwords to
their original values. This password is only provided to the system planner and can
only be used once.