EUCHNER MSC - 8.3.12. Modules SPM0, SPM1, SPM2 (Figure 25)

EUCHNER MSC
148 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
English
FM4 (Figure 22)
SIGNIFICANCE
LED
RECTIFICATION MEASURE
RUN
IN FAIL
EXT FAIL
SEL
IN112
GREEN
RED
RED
ORANGE
YELLOW
Internal fault
OFF
Flashes
2 or 3
times
OFF
Indicates the
physical address
of the module
OFF
Send module to EUCHNER
for repair
Compatibility error
OFF
Flashes
5
times
OFF
Flashes 5
times
Firmware version not
compatible with MSC-CB.
Send to EUCHNER for
firmware upgrade.
Error during communi-
cation with base unit
OFF
Flashes
5
times
OFF
OFF
Restart system.
If the problem persists,
send FM4 to EUCHNER
for repair.
Error in another expan-
sion module or MSC-CB
OFF
ON
OFF
OFF
Restart system.
Check which module is
in the ERROR mode.
Expansion module of
the same type with the
same address detected
OFF
Flashes
5
times
Flashes
5 times
OFF
Change address of the
module (see
NODE_SEL)
Internal node
detection error
OFF
Flashes
3 times
OFF
Flashes 3 times
OFF
Send to EUCHNER for
repair
Table 39 Troubleshooting FM4
Figure 22 FM4