Selection SENSOR
Blind Time: Only if "Muting Close" = "Curtain": Should be selected if, for instance, it is
known that after the end of the muting, objects may protrude beyond the pallet and may
occupy the light curtain, as a result the INPUT input is set to "0" (FALSE). During the blind
time the INPUT input remains "1" (TRUE). The blind time can be between 250 ms and 1 s.
Sensor Time: Defines the maximum time (between 2 s and 5 s) between the activation of
two muting sensors.