StartUp Test: If selected, the test is undertaken on switching on the external components
(emergency stop). This test is undertaken by pressing and releasing the emergency stop
to carry out one complete function test and to activate the output. This test is only re-
quested on starting the machine (on switching on the module).
Filter (ms): This parameter makes it possible to filter the signals that are received from
the emergency stop. The filter can be set to between 3 and 250 ms and removes any con-
tact bounce. The time set for the filter affects the calculation of the total response time of
the module.
With Simultaneity: If selected, the simultaneous switching of the signals received from
the emergency stop is checked.
Simultaneity (ms): This control is only available if the previous parameter has been se-
lected. Using this value you can define the maximum time (in ms) between the switching
of the two signals that are received from the emergency stop.
Enable Out Error: If selected, an error detected by the function block is signaled.
Item Description: Here you can enter a functional description for the component. The text
is displayed in the upper part of the symbol.