out one complete function test and to activate the output. This test is only requested on
starting the machine (on switching on the module).
Filter (ms): This parameter makes it possible to filter the signals that are received from
the external contactors. The filter can be set to between 3 and 250 ms and removes any
contact bounce. The time set for the filter affects the calculation of the total response
time of the module.
With Simultaneity: If selected, the simultaneous switching of the signals received from
the external contacts is checked.
Simultaneity (ms): This control is only available if the previous parameter has been se-
lected. Using this value you can define the maximum time (in ms) between the switching
of the two different signals that are received from the external contacts.
Enable Error Out: If selected, an error detected by the function block is signaled.
Item Description: Here you can enter a functional description for the component. The text
is displayed in the upper part of the symbol.