QUANTUM™ COMPRESSOR CONTROL PANEL S90-010 O
OPERATION Page 95
High Auxiliary Analog #9 Alarm - The Auxiliary Analog
#9 value was greater than or equal to the high Auxiliary
Analog #9 alarm setpoint for its time delay.
High Auxiliary Analog #9 Shutdown - The Auxiliary
Analog #9 value was greater than or equal to the high
Auxiliary Analog #9 shutdown setpoint for its time delay.
High Discharge Temperature Alarm - The Discharge
Temperature was greater than or equal to the High
Discharge Temperature Alarm setpoint for its time delay.
High Discharge Temperature Shutdown - The
Discharge Temperature was greater than or equal to the
High Discharge Temperature Shutdown setpoint for its
time delay.
High Discharge Pressure Alarm - The Discharge
Pressure was greater than or equal to the active High
Discharge Pressure Alarm setpoint for its time delay.
High Discharge Pressure Shutdown - The Discharge
Pressure was greater than or equal to the active High
Discharge Pressure Shutdown setpoint for its time delay.
High Economizer Alarm - The Auxiliary Analog #10 value
was greater than or equal to the high Auxiliary Analog #10
alarm setpoint for its time delay.
High Economizer Shutdown - The Auxiliary Analog #10
value was greater than or equal to the high Auxiliary
Analog #10 shutdown setpoint for its time delay.
High Entering Process Temperature Alarm - The
Entering Process Temperature was greater than or equal
to the High Entering Process Temperature Alarm setpoint
for its time delay.
High Entering Process Temperature Shutdown - The
Entering Process Temperature was greater than or equal
to the High Entering Process Temperature Shutdown
setpoint for its time delay.
High Liquid Level Shutdown - The corresponding input
module was de-energized.
High Manifold Pressure Alarm - This alarm applies if
Engine Drive was enabled. When the Manifold Pressure
exceeds this setpoint, an alarm will occur.
High Manifold Pressure Shutdown - This shutdown
applies if Engine Drive was enabled. When the Manifold
Pressure exceeds this setpoint, an alarm will occur.
High Motor Current Alarm - The Motor Amps was
greater than or equal to the High Motor Amps Alarm
setpoint for its time delay.
High Motor Current Shutdown - The motor amps was
greater than or equal to the High Motor Amps Shutdown
setpoint for its time delay.
High Oil Filter Pressure Alarm - The Oil Filter Pressure
was greater than or equal to the High Filter Pressure
Alarm setpoint for its time delay.
High Oil Filter Pressure Shutdown - The Oil Filter
Pressure was greater than or equal to the High Filter
Pressure Shutdown setpoint for its time delay.
High Oil Temperature Alarm - The Oil Temperature was
greater than or equal to the High Oil Temperature Alarm
setpoint for its time delay.
High Oil Temperature Shutdown - The Oil Temperature
was greater than or equal to the High Oil Temperature
Shutdown setpoint for its time delay.
High RPM Alarm - This alarm applies if Engine or Turbine
Drive was enabled. If the RPM's of the motor exceeds this
setpoint, an alarm will occur.
High RPM Shutdown - This shutdown applies if Engine or
Turbine Drive was enabled. If the RPM's of the motor
exceeds this setpoint, a shutdown will occur.
Hi Suction Pressure Alarm - The Suction Pressure was
greater than or equal to the active High Suction Pressure
Alarm setpoint for its time delay.
Hi Suction Pressure Shutdown - The Suction Pressure
was greater than or equal to the active High Suction
Pressure Shutdown setpoint for its time delay.
Insufficient Main Oil Pressure Shutdown - The Slide
Valve is greater than 50% and the Oil Pressure (PSIA) is
less than or equal to the Suction Pressure (PSIA)
multiplied by 1.5 and then added to 15.0.
Liquid Slug Alarm - This alarm is triggered off of a
sudden decrease in Discharge Temperature that is greater
than the Liquid Slug Alarm setpoint for a five (5) second
period. That is, if the Discharge Temperature is 130
degrees F, and the Liquid Slug Alarm setpoint is 10
degrees F, then a sudden drop in Discharge Temperature
from 130 to 120 degrees F within a five second period will
generate an alarm condition.
Liquid Slug Shutdown This shutdown is triggered off of a
sudden decrease in Discharge Temperature that is greater
than the Liquid Slug Shutdown setpoint for a five (5)
second period. That is, if the Discharge Temperature is
130 degrees F, and the Liquid Slug Shutdown setpoint is
20 degrees F, then a sudden drop in Discharge
Temperature from 130 to 110 degrees F within a five
second period will generate a shutdown condition.
Low Auxiliary Analog #1 Alarm - The Auxiliary Analog
#1 value was less than or equal to the low Auxiliary
Analog #1 alarm setpoint for its time delay.
Low Auxiliary Analog #1 Shutdown - The Auxiliary
Analog #1 value was less than or equal to the low
Auxiliary Analog #1 shutdown setpoint for its time delay.
Low Auxiliary Analog #2 Alarm - The Auxiliary Analog
#2 value was less than or equal to the low Auxiliary
Analog #2 alarm setpoint for its time delay.
Low Auxiliary Analog #2 Shutdown - The Auxiliary
Analog #2 value was less than or equal to the low
Auxiliary Analog #2 shutdown setpoint for its time delay.
Low Auxiliary Analog #3 Alarm - The Auxiliary Analog
#3 value was less than or equal to the low Auxiliary
Analog #1 alarm setpoint for its time delay.
Low Auxiliary Analog #3 Shutdown - The Auxiliary
Analog #3 value was less than or equal to the low
Auxiliary Analog #3 shutdown setpoint for its time delay.
Low Auxiliary Analog #4 Alarm - The Auxiliary Analog
#4 value was less than or equal to the low Auxiliary
Analog #4 alarm setpoint for its time delay.