S90-010 O FRICK
®
QUANTUM™ COMPRESSOR CONTROL PANEL
Page 96 OPERATION
Low Auxiliary Analog #4 Shutdown - The Auxiliary
Analog #4 value was less than or equal to the low
Auxiliary Analog #4 shutdown setpoint for its time delay.
Low Auxiliary Analog #5 Alarm - The Auxiliary Analog
#5 value was less than or equal to the low Auxiliary
Analog #5 alarm setpoint for its time delay.
Low Auxiliary Analog #5 Shutdown - The Auxiliary
Analog #5 value was less than or equal to the low
Auxiliary Analog #5 shutdown setpoint for its time delay.
Low Auxiliary Analog #6 Alarm - The Auxiliary Analog
#6 value was less than or equal to the low Auxiliary
Analog #6 alarm setpoint for its time delay.
Low Auxiliary Analog #6 Shutdown - The Auxiliary
Analog #6 value was less than or equal to the low
Auxiliary Analog #6 shutdown setpoint for its time delay.
Low Auxiliary Analog #7 Alarm - The Auxiliary Analog
#7 value was less than or equal to the low Auxiliary
Analog #7 alarm setpoint for its time delay.
Low Auxiliary Analog #7 Shutdown - The Auxiliary
Analog #7 value was less than or equal to the low
Auxiliary Analog #7 shutdown setpoint for its time delay.
Low Auxiliary Analog #8 Alarm - The Auxiliary Analog
#8 value was less than or equal to the low Auxiliary
Analog #8 alarm setpoint for its time delay.
Low Auxiliary Analog #8 Shutdown - The Auxiliary
Analog #8 value was less than or equal to the low
Auxiliary Analog #8 shutdown setpoint for its time delay.
Low Auxiliary Analog #9 Alarm - The Auxiliary Analog
#9 value was less than or equal to the low Auxiliary
Analog #9 alarm setpoint for its time delay.
Low Auxiliary Analog #9 Shutdown - The Auxiliary
Analog #9 value was less than or equal to the low
Auxiliary Analog #9 shutdown setpoint for its time delay.
Low Economizer Alarm - The Auxiliary Analog #10 value
was less than or equal to the low Auxiliary Analog #10
alarm setpoint for its time delay.
Low Economizer Shutdown - The Auxiliary Analog #10
value was less than or equal to the low Auxiliary Analog
#10 shutdown setpoint for its time delay.
Low Entering Process Temperature Alarm - The
Entering Process Temperature was less than or equal to
the Low Entering Process Temperature Alarm setpoint for
its time delay.
Low Entering Process Temperature Shutdown - The
Entering Process Temperature was less than or equal to
the Low Entering Process Temperature Shutdown setpoint
for its time delay.
Low Main Oil Injection Pressure Shutdown - This
shutdown can occur if Oil Injection was enabled. The Oil
Injection Pressure (channel 15, Analog Board 2) must
greater than or equal the Suction Pressure times 1.5, plus
the setpoint to be in the safe condition, otherwise this
shutdown will occur.
Low Motor Current Shutdown - This shutdown message
is issued if, while the compressor was running, the Motor
Amps reading was less than or equal to the Low Motor
Amps Shutdown setpoint.
Low Oil Pressure Alarm - The compressor was running.
Either the Oil Pressure of a running pump was less than or
equal to the Low Oil Pressure Alarm setpoint, or the Oil
Pressure of a not running pump was less than or equal to
the Low Oil Pressure Alarm setpoint for its time delay.
Low Oil Pressure Shutdown - The compressor was
running. Either the Oil Pressure of a running pump was
less than or equal to the Low Oil Pressure Shutdown
setpoint, or the Oil Pressure of a not running pump was
less than or equal to the Low Oil Pressure Shutdown
setpoint for its time delay.
Low Oil Separator Temperature Alarm - The Oil
Separator Temperature was less than or equal to the Low
Oil Separator Temperature Alarm setpoint for its time
delay.
Low Oil Separator Temperature Shutdown - The Oil
Separator Temperature was less than or equal to the Low
Oil Separator Temperature Alarm setpoint for its time
delay.
Low Oil Temperature Alarm - The Oil Temperature was
less than or equal to the Low Oil Temperature Alarm
setpoint for its time delay.
Low Oil Temperature Shutdown - The Oil Temperature
was less than or equal to the Low Oil Temperature
Shutdown setpoint for its time delay.
Low Process Temperature Alarm - Process
Temperature was the active Capacity Control and the
Process Temperature was less than or equal to the Low
Process Temperature Alarm setpoint for its time delay.
This Process Temperature is the Leaving Process
Temperature.
Low Process Temperature Shutdown - Process
Temperature was the active Capacity Control and the
Process Temperature was less than or equal to the Low
Process Temperature Shutdown setpoint for its time delay.
This Process Temperature is the Leaving Process
Temperature.
Low RPM Alarm - This alarm applies if Engine or Turbine
Drive was enabled. If the RPM's of the motor drops below
this setpoint, an alarm will occur.
Low RPM Shutdown - This shutdown applies if Engine or
Turbine Drive was enabled. If the RPM's of the motor
drops below this setpoint, a shutdown will occur.
Low Suction Pressure Alarm - The Suction Pressure
was less than or equal to the active Low Suction Pressure
Alarm setpoint for its time delay.
Low Suction Pressure Shutdown - The Suction
Pressure was less than or equal to the active Low Suction
Pressure Shutdown setpoint for its time delay.
Maintenance - Alarm - This alarm is generated from the
Maintenance Schedule. It indicates that the amount of
hours in the Service Every column has been exceeded.
The alarm name may be custom named by the operator.
This is purely an informational maintenance alarm, and
there is no shutdown associated it.
Missing Oil Pressure Alarm - The Oil Pressure (PSIA) is
less than the Suction Pressure (PSIA) multiplied by 1.1
and then added to 15.0, then delayed by 25 sec.