QUANTUM™ COMPRESSOR CONTROL PANEL S90-010 O
OPERATION Page 97
Missing Oil Pressure Shutdown 1 - The Oil Pressure
(PSIA) is less than the Suction Pressure (PSIA) multiplied
by 1.1 and then added to 15.0, then delayed by 2 min.
Missing Oil Pressure Shutdown 2 - The Oil Pressure
(PSIA) is less than the Suction Pressure (PSIA) added to
15.0, then delayed by 25 sec.
Motor Stator # 1 Temp. Alarm - If Motor Stator #1
temperature sensor registers a reading that is higher than
the value that has been set for the Motor Stator #1 Temp.
Alarm, for the period of time as set for the Motor Stator #1
Temp. Alarm Delay, an Alarm will be generated.
Motor Stator # 1 Shutdown Alarm - If Motor Stator #1
temperature sensor registers a reading that is higher than
the value that has been set for the Motor Stator #1 Temp.
Shutdown, for the period of time as set for the Motor
Stator #1 Temp. Shutdown Delay, a Shutdown will be
generated.
Motor Stator # 2 Temp. Alarm - If Motor Stator #2
temperature sensor registers a reading that is higher than
the value that has been set for the Motor Stator #2 Temp.
Alarm, for the period of time as set for the Motor Stator #2
Temp. Alarm Delay, an Alarm will be generated.
Motor Stator # 2 Shutdown Alarm - If Motor Stator #2
temperature sensor registers a reading that is higher than
the value that has been set for the Motor Stator #2 Temp.
Shutdown, for the period of time as set for the Motor
Stator #2 Temp. Shutdown Delay, a Shutdown will be
generated.
Motor Stator # 3 Temp. Alarm - If Motor Stator #3
temperature sensor registers a reading that is higher than
the value that has been set for the Motor Stator #3 Temp.
Alarm, for the period of time as set for the Motor Stator #3
Temp. Alarm Delay, an Alarm will be generated.
Motor Stator # 3 Shutdown Alarm - If Motor Stator #3
temperature sensor registers a reading that is higher than
the value that has been set for the Motor Stator #3 Temp.
Shutdown, for the period of time as set for the Motor
Stator #3 Temp. Shutdown Delay, a Shutdown will be
generated.
Motor Starter Comm. Fail - Shutdown - It has been
detected that the program is no longer able to
communicate to a RAM DBS Motor Starter.
Oil Level Shutdown - The corresponding input module for
low Oil Level was de-energized for five (5) minutes.
Oil Log Shutdown - Oil log was enabled in Factory Setup
and the Compressor has not started and the Oil Pump has
already run for the fail delay time.
Oil Pressure Sensor Fault - This shutdown message is
issued if the Oil Pressure reading was out of range for its
sensor.
Oil Pump Aux Failure - While starting the Oil Pump, the
Oil Pump Auxiliary input module did not energize within
five (5) seconds, or, while the Oil Pump was running, the
Oil Pump Auxiliary input module de-energized.
Oil Pump #1 Aux. Alarm - While starting Oil Pump #1,
the Oil Pump #1 Auxiliary input module did not energize
within five (5) seconds, or, while this Oil Pump was
running, the Oil Pump #1 Auxiliary input module de-
energized. This indicates Dual Pump Control and Pump
#1 is the lead pump.
Oil Pump #1 Aux. Failure Shutdown - While starting Oil
Pump #1, the Oil Pump #1 Auxiliary input module did not
energize within five (5) seconds, or, while this Oil Pump
was running, the Oil Pump #1 Auxiliary input module de-
energized. This indicates Dual Pump Control and Pump
#1 is the last pump to start.
Oil Pump #2 Aux. Alarm - While starting Oil Pump #2,
the Oil Pump #2 Auxiliary input module did not energize
within five (5) seconds, or, while this Oil Pump was
running the Oil Pump #2 Auxiliary input module de-
energized. This indicates Dual Pump Control and Pump
#2 is the lead pump.
Oil Pump #2 Aux. Failure Shutdown - While starting Oil
Pump #2, the Oil Pump auxiliary input module did not
energize within five (5) seconds, or, while the Oil Pump
was running, the Oil Pump auxiliary input module de-
energized. This indicates Dual Pump Control and Pump
#2 is the last pump to start.
Oil Temperature Sensor Fault - This shutdown message
is issued if the Oil Temperature reading was out of range
for its sensor.
Opposite Shaft Side Drive Vibration Alarm - If the
Opposite Shaft Side Drive Vibration sensor registers a
reading that is higher than the value that has been set for
the Opposite Shaft Side Drive Vibration Alarm, for the
period of time as set for the Opposite Shaft Side Drive
Vibration Alarm Delay, an Alarm will be generated.
Opposite Shaft Side Drive Vibration Shutdown - If the
Opposite Shaft Side Drive Vibration sensor registers a
reading that is higher than the value that has been set for
the Opposite Shaft Side Drive Vibration Shutdown, for the
period of time as set for the Opposite Shaft Side Drive
Vibration Shutdown Delay, a Shutdown will be generated.
Opposite Shaft Side Drive Temp. Alarm - If the
Opposite Shaft Side Drive Temperature sensor registers a
reading that is higher than the value that has been set for
the Opposite Shaft Side Drive Temperature Alarm, for the
period of time as set for the Opposite Shaft Side Drive
Temperature Alarm Delay, an Alarm will be generated.
Opposite Shaft Side Drive Temp. Shutdown - If the
Opposite Shaft Side Drive Temperature sensor registers a
reading that is higher than the value that has been set for
the Opposite Shaft Side Drive Temperature Shutdown, for
the period of time as set for the Opposite Shaft Side Drive
Temperature Shutdown Delay, a Shutdown will be
generated.
Separator Temperature Sensor Fault - This shutdown
message is issued if the Oil Separator Temperature
reading was out of range for its sensor.
Shaft Side Drive Vibration Alarm - If the Shaft Side
Drive Vibration sensor registers a reading that is higher
than the value that has been set for the Shaft Side Drive
Vibration Alarm, for the period of time as set for the Shaft
Side Drive Vibration Alarm Delay, an Alarm will be
generated.
Shaft Side Drive Vibration Shutdown - If the Shaft Side
Drive Vibration sensor registers a reading that is higher
than the value that has been set for the Shaft Side Drive