S90-010 O FRICK
QUANTUM™ COMPRESSOR CONTROL PANEL
Page 98 OPERATION
Vibration Shutdown, for the period of time as set for the
Shaft Side Drive Vibration Shutdown Delay, a Shutdown
will be generated.
Shaft Side Drive Temp. Alarm - If the Shaft Side Drive
Temperature sensor registers a reading that is higher than
the value that has been set for the Shaft Side Drive
Temperature Alarm, for the period of time as set for the
Shaft Side Drive Temperature Alarm Delay, an Alarm will
be generated.
Shaft Side Drive Temp. Shutdown - If the Shaft Side
Drive Temperature sensor registers a reading that is
higher than the value that has been set for the Shaft Side
Drive Temperature Shutdown, for the period of time as set
for the Shaft Side Drive Temperature Shutdown Delay, a
Shutdown will be generated.
Starting Failure - This message may be issued if Engine
or Turbine was enabled, and the start delay period to get
to a running condition has expired.
Starting Superheat Shutdown - This message may be
issued if Superheat was enabled. A shutdown will occur if
TDsat plus temperature setpoint is greater than the
Separator temperature.
Suction End Compressor Vibration Alarm - If the
Suction End Compressor Vibration sensor registers a
reading that is higher than the value that has been set for
the Suction End Compressor Vibration Alarm, for the
period of time as set for the Suction End Compressor
Vibration Alarm Delay, an Alarm will be generated.
Suction End Compressor Vibration Shutdown - If the
Suction End Compressor Vibration sensor registers a
reading that is higher than the value that has been set for
the Suction End Compressor Vibration Shutdown, for the
period of time as set for the Suction End Compressor
Vibration Shutdown Delay, a Shutdown will be generated.
Suction Pressure Sensor Fault - This shutdown
message is issued if the Suction Pressure reading was out
of range for its sensor.
VariSpeed Communications Alarm - If VariSpeed option
if enabled and the Comms communication has failed, this
alarm is shown.