The Web Interface
147
8
[Interlock] When the option is enabled, the two mentioned doors will be interlocked,
allowing only one door to be opened at a time.
[Events]
Set the parameters for the events.
When Door Control is selected in the Function Configuration page (Figure 8-8), these
options become available:
Option Description
Anti-Passback Enables or disables the Anti-Passback function.
Lock Reset Time
Sets the time (1 to 255 sec.) that a door remains open after which
the door will automatically be locked.
Held Open Time
Sets the time (5 to 9999 sec.) that a door can be held open before
an alarm is generated.
Fire Action
Locks or unlocks the door when a fire condition occurs. Otherwise,
remains the door’s current state by selecting Unchanged.
Alarm Continuous
Time
Sets the time (1 to 10 sec.) that the alarm will continuously go off
before it ends.
When Parking Control is selected in the Function Configuration page (Figure 8-8),
these options become available:
Option
Description
Anti-Passback
See the same option above.
Relay On Time
Sets the time (1 to 255 sec.) that a gate remains open after which
the gate will automatically be closed.
Held Open Time
Fire Action
Alarm Continuous
Time
See the same option above.
Note: The Interlock function is not available on the Web interface of GV-AS1010 / 1110 /
210 / 2110 / 2120 / 410 / 4110 / 810 / 8110. To set up interlock function for these models,
go to the Controller Setup page on GV-ASManager.