12.4 Formulae
208
Total harmonic current distortion factor THDIR (%)
Single-phase 2-wire
1P2W
Single-phase 3-wire
1P3W
Three-phase 3-wire
3P3W2M
Three-phase 3-wire
3P3W3M
Three-phase 4-wire
3P4W
THDIR1
THDIR4
THDIR1
THDIR2
THDIR4
THDIR1
THDIR2
THDIR4
THDIR1
THDIR2
THDIR3
THDIR4
THDIR1
THDIR2
THDIR3
THDIR4
Calculate the Discrete Fourier Transform of harmonic RMS current at 2048 points (about once every 10
cycles at 50 Hz or every 12 cycles at 60 Hz).
In the equation above, K indicates the total of orders analyzed.
Select either THDIF or THDIR to calculate the total harmonic current distortion factor.
c: measured channel, k: order for analysis
T
HDIRc
I
ck()
2
k2=
K
Ick()
2
k1=
K
---------------------
100×=
Harmonic voltage phase angle θUk (deg)
Single-phase 2-wire
1P2W
Single-phase 3-wire
1P3W
Three-phase 3-wire
3P3W2M
Three-phase 3-wire
3P3W3M
Three-phase 4-wire
3P4W
θ
U1k
θ
U4k
θ
U1k
θ
U2k
θ
U4k
θ
U12k
θ
U32k
θ
U4k
θ
U12k
θ
U23k
θ
U31k
θ
U4k
θ
U1k
θ
U2k
θ
U3k
θ
U4k
Calculate the Discrete Fourier Transform of harmonic RMS voltage at 2048 points (about once every 10
cycles at 50 Hz or every 12 cycles at 60 Hz).
Three-phase 3-wire indicates the result of harmonic calculation with line-to-line voltage.
Corrects the PLL source fundamental wave to 0° and displays the harmonic voltage phase angle.
When Uckr=Ucki=0
θ
Uk=0°.
The harmonic voltage used in calculations is only taken from integral harmonics.
c: measured channel, k: order for analysis, r: resistance after FFT, i: reactance after FFT
θUck
Uckr
Ucki
--------------
⎩⎭
⎨⎬
⎧⎫
1
tan=
Harmonic current phase angle θIk (deg)
Single-phase 2-wire
1P2W
Single-phase 3-wire
1P3W
Three-phase 3-wire
3P3W2M
Three-phase 3-wire
3P3W3M
Three-phase 4-wire
3P4W
θ
I1k
θ
I4k
θ
I1k
θ
I2k
θ
I4k
θ
I1k
θ
I2k
θ
I4k
θ
I1k
θ
I2k
θ
I3k
θ
I4k
θ
I1k
θ
I2k
θ
I3k
θ
I4k
Calculate the Discrete Fourier Transform of harmonic RMS current at 2048 points (about once every 10
cycles at 50 Hz or every 12 cycles at 60 Hz).
Corrects the PLL source fundamental wave to 0° and displays the harmonic current phase angle.
When Ickr=Icki=0
θ
Ik=0°.
The harmonic current used in calculations is only taken from integral harmonics.
c: measured channel, k: order for analysis, r: resistance after FFT, i: reactance after FFT
θIck
Ickr
Icki
----------- -
⎩⎭
⎨⎬
⎧⎫
1
tan=