EasyManua.ls Logo

Keithley 2510 - Step 3: Congure Selected Function; Step 4: Program Setpoint; Step 5: Set Current Limit; Step 6: Turn Output on

Keithley 2510
244 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3-12 Basic Operation Models 2510 and 2510-AT User’s Manual
Step 3: Congure selected function.
Send the commands to program temperature units, protection limits, sensor type, sensor
parameters, and PID loop constants. For example, the following commands configure the
temperature function:
:UNIT:TEMP CEL Celsius temperature limits
:SOUR:TEMP:PROT 100 Upper temperature limit = 100˚
:SOUR:TEMP:PROT:LOW 10 Lower temperature limit = 10˚
:TEMP:TRAN RTD Select RTD temperature sensor
:TEMP:RTD:TYPE PT100 Select PT100 RTD sensor
:TEMP:RTD:RANG 100 Set 100 range.
:TEMP:CURR:AUTO ON Use default RTD sensor current
:SYST:RSEN ON Enable 4-wire sensing
:SOUR:TEMP:LCON 10 Temperature gain constant = 10
:SOUR:TEMP:LCON:INT 0.5 Temperature integral constant = 0.5
:SOUR:TEMP:LCON:DER 0 Temperature derivative constant = 0
Step 4: Program setpoint.
Program the setpoint for the selected control function. For example, the following com-
mand programs the temperature setpoint to 50˚:
:SOUR:TEMP 50
Step 5: Set current limit.
If required, set the current limit with this command:
:SENS:CURR:PROT<Current_Limit>
Step 6: Turn output on.
Turn the output on to begin PID control by sending the following commands:
:OUTP ON
Step 7: Request readings.
During operation, you can request readings with the :FETCH? query. Note that bus read-
ing elements are controlled with the :FORM:ELEM command. You can also request addi-
tional reading types with the following queries:
:MEAS:POW? Query thermoelectric cooler power
:MEAS:CURR? Query cooler current
:MEAS:TEMP? Query temperature
:MEAS:RES? Query cooler DC resistance
:MEAS:VOLT? Query cooler voltage

Table of Contents

Related product manuals