© KWB – Kraft und Wärme aus Biomasse GmbH IM Easyfire 10/2008 Page 135
16 Suction conveyor, lance + buried tank
16 Suction conveyor, lance + buried tank
16 RA “GL” SUCTION CONVEYOR,
LANCE WITH BURIED TANK
Buried Tank
Protective pipe HT pipe
at least ; 15 cm
Ceiling opening ; 70 mm
Fire-safety collar
Solid ceiling F90
Outline
USP GL with fabric tank
and buried tank
Pellet transport hose
max. length 25 m
Hose Guide
• Max. total lift 5 m
• Max. total lift without step 3 m
• At the latest after 3 m height difference 1 m route horizontally
• All conveyor hose bend radii at least 30 cm.
16.1 Pellet storage room requirements
(FE type GL, fan and lance with buried fabric tank)
Comply with the instructions in points 1.3 to 1.3.2 in the introduction!
Heiz- und Lagerraumausführung – KWB Easyfire GL
KWB Easyfire USP GL
Pellet boiler
with suction system and buried tank
Boiler room
STOP SWITCH
Boiler room door
T30 100/120
Vent opening
Cleaning door
(top)
Sweep door (bottom)
Fire
extinguisher
Buried tank
Boiler room and storage room construction – KWB Easyfire GL
MA-Easyfire 10.2008_EN.indd 135MA-Easyfire 10.2008_EN.indd 135 30.03.2009 13:31:30 Uhr30.03.2009 13:31:30 Uhr