© KWB – Kraft und Wärme aus Biomasse GmbH IM Easyfire 10/2008 Page 19
2 System installation
2 System installation
12.) Take off the cladding
Unscrew the wing screws.
Unhook the rear wall.
Dismount the rear wall
Unscrew the screws of both side cladding elements.
Remove the side cladding
Unhook the side cladding elements.
Unhook the side cladding elements
To convert the system from left orientation to right orientation, continue with point 2.1.2 “Left / right system
conversion”.
The steps for bringing the system into the boiler room in dismantled status are provided in the next section.
2.1.1.2 Bringing the dismantled system into the boiler room
Af ter the system has been prepared to be brought into the boiler room in dismantled status as specified in point 2.1.1.1,
proceed as follows.
11.) Take off the door cladding
Unscrew the side screws of the door cladding.
Take off the door cladding.
Dismount the cladding for transport with the hand truck!
This will prevent damage to the cladding.
Door cladding
MA-Easyfire 10.2008_EN.indd 19MA-Easyfire 10.2008_EN.indd 19 30.03.2009 13:29:52 Uhr30.03.2009 13:29:52 Uhr