© KWB – Kraft und Wärme aus Biomasse GmbH IM Easyfire 10/2008 Page 57
4 Operation, specialist
4 Operation, specialist
4.2.14 Menu item – Rotary Grate
Fuel factor: This factor takes the pellet density (“energy content) into account.The higher the density
the smaller the factor (push-in quantity) that can be selected.Pellets of an average quality
have a pellet factor of 100 %.
Rotary grate: ON: The rotary grate is activated.
OFF: The rotary grate is not activated.
Idle time: Use the idle time to control the duration of rotary grate inactivity. Runtime of 5 sec. is
permanently specified. The factory setting for idle time is 7 min. For pellets with higher ash
content, set the idle time appropriately shorter.
4.3 Menu item – Relay Test
In the relay test all outputs can be switched by hand. In this menu all other control system functions are inactive.
4.3.1 Boiler
Primary relay: This relay switches the main drive motor, the fuel extractor drive motor, the fan, the induced
draft fan, and the boiler circuit pump.
Main motor: Triac main drive motor
Cleaning: Relay, cleaning motor
Ignition: Relay, electrical ignition
The relay can only be switched on if the fan is running. (Prevents destruction of the electrical
heating elements due to overheating)
Ash removal
system:
ON: Ash worm runs in continuous operation,
OFF: Ash worm does not run
MA-Easyfire 10.2008_EN.indd 57MA-Easyfire 10.2008_EN.indd 57 30.03.2009 13:30:08 Uhr30.03.2009 13:30:08 Uhr