4 Operation, specialist
4.2.6 Boiler pump
Speed: Setting of the maximum speed of the boiler circuit pump in %.
4.2.7 Language
System operation is possible in German, Italian, French, Slovenian, English, and Spanish.
4.2.8 Second boiler
If the plug-in module is installed, a log wood boiler (second boiler) can be controlled:
Switchover at: If this temperature is exceeded the pellet boiler is switched off.
(Status of the second boiler “Normal mode”)
Overheating at: When this temperature is exceeded, all heat consumers are switched to maximum heat
intake. (Status of the second boiler “Overheating”)
Boiler pump: On: The boiler pump of the automatic boiler runs in tandem with the second boiler pump.
Off: The boiler pump of the automatic boiler does not run in tandem.
The hydraulic circuit of a second boiler (log wood boiler) is executed in accordance with diagram no. MBEH0005 in
section 17.
4.2.9 Cleaning
Time: At this time the heat exchanger cleaning system is switched on for 40 seconds. Ash
compaction is operated simultaneously with automatic boiler cleaning. There is a swivelling
flap in the ash box that is activated via a linkage mechanism from the cleaning motor. The
mixer and pump blocking protection are coupled with the heat exchanger cleaning system.
The pumps and mixers are also activated for 20 s to prevent blocking after a longer period
of standstill
.
Information on ash removal is provided in the operating manual, sections 4, 5, and 6.