18.2 Hydraulic diagrams
Base module with weather-sensitive control system MBEH0003_a sheet 2/2
Menu basic settings
Parameters Settings
Return ow boost Bypass pump
Network settings Boiler External 2 Heat to target 2
Power output Heating mode
Boiler dependence Yes
Heating circuit/
heating circuit 0 Room sensor Boiler/0
Outdoor sensor Boiler
Function No
Group no. 0
Heating circuit/
heating circuit 1 Room sensor Boiler/1
Outdoor sensor Boiler
Function Yes
Group no. 0
Heating circuit/
heating circuit 2 Room sensor DRCU1
Outdoor sensor Boiler
Function Yes
Group no. 0
DHWC/DHWC 0 Function Yes or before
Group no. 0
Buer/Buer 0 Function No
Digital remote control/ Outdoor sensor Boiler
Digital remote control 1 Heating circuit 1 – 2
DHWC 0 – 0
Buer ---
Hardware Heating circuit modules 0
Digital remote control 1
Plu
-in modules O
System description:
The hydraulic system consists of the boiler circuit (without main pump), and a distributor that is under
pressure. The return flow boost is executed via a bypass pump (4) in fixed speed execution, which is
activated via speed-regulation. Speed level switching must be set to the highest speed. The basic module
for boiler/DHWC & buffer control is equipped with a weather-sensitive control system for 2 heating circuits
(option). One heating circuit is equipped with an analogue room control unit (option), the second heating
circuit is equipped with a digital room control unit (option) for remote control.
Subject to change!
Tech. data sheet HYD-USP-MBEH0003_a, sheet 2/2, Date: 13-07-06 StHo