Commissioning
8200SHB0199
5-9
4.Set slip compensation
(
C
0
2
1
)
:
Rough setting according to motor data:
4
.
S
e
t
s
l
i
c
o
m
e
s
a
t
i
o
(C021):
s
n
Nsyn
n
r
n
Nsyn
ô
100 %
n
Nsyn
f
dr
ô
60
p
s Slip constant (C021)
n
Nsyn
Synchronous motor speed [min
-1
]
n
r
Rated speed to motor nameplate [min
-1
]
f
dr
Rated frequency to motor nameplate [Hz]
p No. of pole pairs (1, 2, 3, ...)
Precise setting:
-
Correct C021 until no load-dependent speed drop occurs in the required speed range between
idle running and max. motor load.
-
If the values under C021 are too high, the drive may become instable (overcompensation).
-
In the field frequency range between 5 Hz ... 50 Hz (87 Hz)the deviation of the rated speed is
$ 1 % (guide value). In field-weakening operation, the fault increases.
Important
-
The change from V/f-characteristic control to motor-current control should only be carried out
when the controller is inhibited.
-
The idle current of the motor (magnetising current) must not exceed the rated current of the
controller.
-
With very small friction values, it is possible that a phase offset of up to 180 occurs at the motor
shaft when enabling the controller.