Commissioning
8200SHB0199
5-11
3.Set V
min
boost (C016). Load-dependent boost of the motor voltage in the field frequency range below the V/f-rated
frequency. C016 acts as gain factor of the auto-boost function.
Adjustment
In general, an adjustment is not necessary. An optimisation can be advantageous:
For drives with very high starting torques:
A Operate the motor under load.
B Select the frequency setpoint.
C Increase V
min
until the required motor current (torque) occurs.
If the setting of V
min
is too high, a positive-feedback effect can occur and activate the TRIP
”overcurrent” (OCx).
For drives with square load torques (fans, pumps):
A Operate the motor under load.
B Select the frequency setpoint.
C Adapt V
min
until the motor is running steadily and smoothly over the whole frequency range.
If the setting of V
min
is too high, the TRIP ”overcurrent” (OCx) can be activated and lead toan
excessive motor temperature.
For drives with special motors:
A Operate the motor under load.
B Select the frequency setpoint.
C Increase V
min
until the required motor current (torque) occurs.
If the setting of V
min
is too high, a positive-feedback effect can occur and activate the TRIP
”overcurrent” (OCx).
D Check the current consumption during idle running when no load is applied.
4.Set the slip compensation
(
C
0
2
1
)
.
Rough setting according to motor data:
4
.
S
e
t
t
e
s
l
i
c
o
m
e
s
a
t
i
o
(C021).
s
n
Nsyn
n
r
n
Nsyn
ô
100 %
n
Nsyn
f
dr
ô
60
p
s Slip constant (C021)
n
Nsyn
Synchronous motor speed [min
-1
]
n
r
Rated speed to motor nameplate [min
-1
]
f
dr
Rated frequency to motor nameplate [Hz]
p No. of pole pairs (1, 2, 3, ...)
Precise setting:
-
Correct C021 until no load-dependent speed drop occurs in the required speed range between
idle running and max. motor load.
-
If the values under C021 are too high, the drive may become instable (overcompensation).
-
In the field frequency range between 5 Hz ... 50 Hz (87 Hz)the deviation of the rated speed is
$ 1 % (guide value). In field-weakening operation, the fault increases.