Configuration
8200SHB0199
7-89
Code IMPORTANTPossible settingsNameCode IMPORTANT
InfoChoiceLenze
Name
C021 Slip compensation 0.0* -50.0 {0.1 %} 50.0 Page 7-28 * If C014 = -2-, -3-,
controller dependent
0.0 0.0 {0.1 %} 20.0 If C014 = -4-
C022 I
max
limit
(motor mode)
150 30 {1 %} 150 Page 7-17
C023 I
max
limit
(generator mode)
80 30 {1 %} 150 Page 7-17 The current-limit
controller for operation
in generator mode is
notactiveat30%.
C026 Offset adjustment
analog input
0.00 -10.00 {0.01 V} 10.00 Page 7-40 C026 < 0 V
-
f
dmin
can fall below
the value set under
C010
C027 Scaling factor of
analog input
100.0 -200.0 {0.1 %} 200.0 Page 7-40
C034¤ Master current -0- -0- 0 to20 mA /
0to5V/0to10V
-1- 4 to20 mA
Page 7-40
C035*¤ Selection DC brake -0- -0- Selection of brake voltage under
C036
-1- Selection of brake current under
C036
Page 7-56
C036 Voltage/current for
DCB
* 0.00 {0.02 %} 150.00 Page 7-56 *depends on the unit
C037 JOG value 1 20.00 -480.00 {0.02 Hz} 480.00 Page 7-43
C038 JOG value 2 30.00 -480.00 {0.02 Hz} 480.00 Page 7-43
C039 JOG value 3 40.00 -480.00 {0.02 Hz} 480.00 Page 7-43
C040 Controller enable * -0- Controller inhibited
-1- Controller enabled
Page 7-62
C043 TRIP reset * -0- No current fault
-1- Current fault
*see Operating
Instructions 2102
C046 Frequency setpoint * -480.00 {0.02 %} 480.00 Page 7-62
C047* Current setpoint
I
max
limit value
Page 7-62 Displayonly[%]
I
max
limit value (C022)
C049* Additional setpoint Page 7-47,
7-62
Display only
-
Only if C005 = 1, 2
C050* Output frequency Page 7-62
C054* Motor current Page 7-62,
7-65
Displayonly[A]
C056* Unit load Page 7-62 Displayonly[%]
C061* Heat sink
temperature
Page 7-62 Displayonly[°C]