9400 regenerative power supply module | Parameter setting
Diagnostics & fault analysis
Error messages
214 L EDS94ARNExxxx EN 2.3 - 06/2014
 
Safety module has been changed [0x00680018]
Combination MXI1/MXI2 not possible [0x00680019]
Firmware has been changed [0x0068001a]
Memory module: Faulty file system [0x0068001c]
Firmware incompatible to control card [0x0068001e]
Combination memory module/device not possible [0x0068001f]
Response (Lenze setting printed in bold)
 None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information
Cause Remedy
The safety module has been changed since the last 
mains switching.
- (Only information or warning locked if the hardware 
type has changed as well.)
Response (Lenze setting printed in bold)
 None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information
Cause Remedy
The combination of the extension modules plugged into 
the module slots MXI1 & MXI2 is not supported.
Use a permitted module combination.
Response (Lenze setting printed in bold)
 None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information
Cause Remedy
The firmware of the operating system has been updated. - (Information only)
Response (Lenze setting printed in bold)
 None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information
Cause Remedy
Memory module is plugged in incorrectly or is defective.  • Plug in the memory module correctly.
 • Exchange defective memory module.
Response (Lenze setting printed in bold)
 None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information
Cause Remedy
Firmware is not compatible with the hardware. Transfer the compatible firmware.
Response (Lenze setting printed in bold)
 None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information
Cause Remedy
The memory module used is not supported by the 
regenerative power supply module according to the 
licence model.
Plug in supported memory module and switch the 
mains.
 • The regenerative power supply module only supports 
the MM220 memory module (licence: Motion Control 
HighLevel).