EDS94ARNExxxx EN 2.3 - 06/2014 L 213
9400 regenerative power supply module | Parameter setting
Diagnostics & fault analysis
Error messages
Incorrect memory module [0x00680012]
Incorrect safety module [0x00680013]
Power stage has been changed [0x00680014]
MXI1: Module has been changed [0x00680015]
MXI2: Module has been changed [0x00680016]
Memory module has been changed [0x00680017]
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The memory module is not supported by the operating
system.
Use a different module.
Please contact Lenze.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
A safety module is inserted in the regenerative power
supply module. The regenerative power supply module
does not support safety engineering.
Use SM0 safety module (without safety engineering).
Then, restart the controller.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The power section has been changed since the last mains
switching.
- (Only information or warning locked if the hardware
type has changed as well.)
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The extension module in the module slot MXI1 has been
changed since the last mains switching.
- (Only information or warning locked if the hardware
type has changed as well.)
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The extension module in the module slot MXI2 has been
changed since the last mains switching.
- (Only information or warning locked if the hardware
type has changed as well.)
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The memory module has been changed since the last
mains switching.
- (Only information or warning locked if the hardware
type has changed as well.)