EDS94ARNExxxx EN 2.3 - 06/2014 L 239
9400 regenerative power supply module | Parameter setting
Diagnostics & fault analysis
Error messages
MXI2: Ethernet module is missing or incompatible [0x008c0012]
MXI1: ICM module is missing or incompatible [0x008c0015]
MXI2: ICM module is missing or incompatible [0x008c0016]
MXI1: CAN module is missing or incompatible [0x008c0017]
MXI2: CAN module is missing or incompatible [0x008c0018]
Parameter set faulty [0x00900000]
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The communication module E94AYCEN (Ethernet) in
module slot MXI2 is incompatible with the application.
Use communication module supported by the
application.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The ICM extension module in module slot MXI1 is
incompatible with the application.
Use extension module supported by the application.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The ICM extension module in module slot MXI2 is
incompatible with the application.
Use extension module supported by the application.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The CANopen communication module in module slot
MXI1 is incompatible with the application.
Use communication module supported by the
application.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The CANopen communication module in module slot
MXI2 is incompatible with the application.
Use communication module supported by the
application.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Parameter set is invalid. Transfer parameter set from the Engineer to the
regenerative power supply module and save it with
C00002
="11".