EDS94ARNExxxx EN 2.3 - 06/2014 L 245
9400 regenerative power supply module | Parameter setting
Diagnostics & fault analysis
Error messages
CAN module (MXI1): Invalid node address 0 [0x009d0001]
CAN module (MXI1): Basic configuration invalid [0x009d0002]
CAN module (MXI1): Heartbeat error index 1 ... 32 [0x009e0000 ... 0x009e001f]
CAN module (MXI1): Lifeguarding error [0x009e0020]
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
CANopen communication module in MXI1: Initialisation
error
The hardware assignment of the node address has
been selected via DIP switch and the DIP switches for
the node address are set to zero.
Note: Instead of the impermissible node address 0 the
node address 1 is used.
Set the DIP switches to a node address unequal 0 and
restart the controller.
Activate the node address assignment by means of
software by changing the position of DIP switch 2 and
restart the controller.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
CANopen communication module in MXI1:
Configuration error
Faulty download of an Engineer or PLC Designer
project
Invalid CAN settings according to DS301V402 in the
Engineer or PLC Designer.
Repeat download
Correct CAN settings in the project and regenerate
project.
Response (Lenze setting printed in bold) Setting: C13613/1...32 ( adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
CANopen communication module in MXI1: Cyclic node
monitoring
Node has not received a heartbeat telegram from
node 1 ... 32 within the defined time.
Reactivate CAN node by mains switching, restart of
the regenerative power supply module,
(C00002
="11000") or CAN reset node.
Reparameterise the heartbeat producer monitoring
time or switch off monitoring and reset locked error
status, if necessary.
Tip: Save the current parameter set before mains
switching and restarting the regenerative power supply
module (C00
002="11").
Response (Lenze setting printed in bold) Setting: C13614 ( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
CANopen communication module in MXI1: Cyclic node
monitoring
Slave response: Maximum time between two node
guarding telegrams (remote transmission request
telegram) from the master has been exceeded.
Reparameterise the life guarding monitoring time or
switch off monitoring.