9400 regenerative power supply module | Parameter setting
Parameter reference
Parameter list | C00064
278 L EDS94ARNExxxx EN 2.3 - 06/2014
C00064
C00065
C00068
C00069
C00070
C00071
C00075
Parameter | Name:
C00064 | Device utilisation (Ixt)
Data type: UNSIGNED_32
Index: 24511
d
= 5FBF
h
Device utilisation during the last 180 seconds
C00064 > 100 % activates error (OC5).
Error reset only possible if C00064 < 95 %.
Display range (min. value | unit | max. value)
0 % 250
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00065 | Ext. 24-V voltage
Data type: INTEGER_32
Index: 24510
d
= 5FBE
h
Display range (min. value | unit | max. value)
0.0 V 1000.0
Read access Write access CINH PLC STOP No transfer Scaling factor: 10
Parameter | Name:
C00068 | Capacitor temperature
Data type: INTEGER_32
Index: 24507
d
= 5FBB
h
Display range (min. value | unit | max. value)
-200 °C 200
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00069 | CPU temperature
Data type: INTEGER_32
Index: 24506
d
= 5FBA
h
Display range (min. value | unit | max. value)
-200 °C 200
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00070 | DC bus voltage ctrl. gain
Data type: UNSIGNED_32
Index: 24505
d
= 5FB9
h
Note: This parameter is only effective in closed-loop operation (in preparation).
Setting range (min. value | unit | max. value) Lenze setting
0.00000 Nm/rpm 20000.00000 0.00400 Nm/rpm
Read access Write access CINH PLC STOP No transfer Scaling factor: 100000
Parameter | Name:
C00071 | DC bus voltage ctrl. reset time
Data type: UNSIGNED_32
Index: 24504
d
= 5FB8
h
Note: This parameter is only effective in closed-loop operation (in preparation).
Setting range (min. value | unit | max. value) Lenze setting
1.0 ms 6000.0 50.0 ms
Read access Write access CINH PLC STOP No transfer Scaling factor: 10
Parameter | Name:
C00075 | Current controller gain
Data type: UNSIGNED_32
Index: 24500
d
= 5FB4
h
Note: This parameter is only effective in closed-loop operation (in preparation).
Setting range (min. value | unit | max. value) Lenze setting
0.00 V/A 750.00 30.00 V/A
Read access Write access CINH PLC STOP No transfer Scaling factor: 100