EDS94ARNExxxx EN 2.3 - 06/2014 L 317
9400 regenerative power supply module | Parameter setting
Parameter reference
Parameter list | C00591
C00591
C00594
C00595
Parameter | Name:
C00591 | Resp. to CAN-RPDOx error
Data type: UNSIGNED_8
Index: 23984
d
= 5DB0
h
Response if the corresponding CAN RPDO has not been received within the configured time or with the configured
sync.
"CAN on board" system bus
Selection list (Lenze setting printed in bold)
1Fault
2Trouble
4 Warning locked
5 Warning
6 Information
0 No response
Subcodes Lenze setting Information
C00591/1 0: No response Response to non-received RPDO1 ... RPDO4
C00591/...
C00591/4
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00594 | Resp. to failure t. sensor filter
Data type: UNSIGNED_32
Index: 23981
d
= 5DAD
h
Response to filter temperature sensor error.
• The response to a too high filter temperature via PTC input T1/T2 can be selected in C00585
.
Selection list (Lenze setting printed in bold)
1Fault
5 Warning
0 No response
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00595 | Resp. to CAN bus OFF
Data type: UNSIGNED_8
Index: 23980
d
= 5DAC
h
Response if CAN node switches to the bus off state.
"CAN on board" system bus
Selection list (Lenze setting printed in bold)
1Fault
2Trouble
4 Warning locked
5 Warning
6 Information
0 No response
Read access Write access CINH PLC STOP No transfer