EDS94ARNExxxx EN 2.3 - 06/2014 L 319
9400 regenerative power supply module | Parameter setting
Parameter reference
Parameter list | C00604
C00604
C00610
C00611
C00612
Parameter | Name:
C00604 | Resp. to device overload > C00123
Data type: UNSIGNED_32
Index: 23971
d
= 5DA3
h
Response if adjustable "I x t" warning threshold (C00123) is reached.
Selection list (Lenze setting printed in bold)
1Fault
5 Warning
0 No response
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00610 | Resp. to failure heatsink fan
Data type: UNSIGNED_32
Index: 23965
d
= 5D9D
h
Response if fan speed of heatsink fan is too low.
Selection list (Lenze setting printed in bold)
1Fault
5 Warning
0 No response
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00611 | Resp. to failure integral fan
Data type: UNSIGNED_32
Index: 23964
d
= 5D9C
h
Response if fan speed of interior fan is too low.
Selection list (Lenze setting printed in bold)
1Fault
5 Warning
0 No response
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00612 | Resp. to CAN node guarding error
Data type: UNSIGNED_8
Index: 23963
d
= 5D9B
h
Response of master if the corresponding node guarding response is not received.
"CAN on board" system bus: node guarding protocol
Selection list (Lenze setting printed in bold)
1Fault
2Trouble
4 Warning locked
5 Warning
6 Information
0 No response
Subcodes Lenze setting Information
C00612/1 0: No response Response to non-received telegram for monitoring entry
1 ... 32
C00612/...
C00612/32
Read access Write access CINH PLC STOP No transfer