Chapter 9. Installation and Wiring
9-1
Chapter 9. Installation and Wiring
9.1 Installation
9.1.1 Installation Environment
This unit has high reliability regardless of its installation environment, but be sure to check the following for system reliability.
1) Environment requirements
Avoid installing this unit in locations which are subjected or exposed to:
(1) Water leakage and dust.
(2) Continuous shocks or vibrations.
(3) Direct sunlight.
(4) Dew condensation due to rapid temperature change.
(5) Higher or lower temperatures outside the range of 0 to 50
(6) Relative humidity outside the range of 5 to 85%
(7) Corrosive or flammable gases
2) Precautions during installing
(1) During drilling or wiring, do not allow any wire scraps to enter into the XGT Panel.
(2) Install it on locations that are convenient for operation.
(3) Make sure that it is not located on the same panel that high voltage equipment located.
(4) Make sure that the distance from the walls of duct and external equipment be 50mm or more.
3) Heat protection design of control box
(1) When installing the XGT Panel in a closed control box, be sure to design heat protection of control box with consideration
of the heat generated by the XGT Panel itself and other devices. The circulation of air using a ventilation fan might affect
to the XGT Panel caused by an inflow of gas or dust.
(2) It is recommended that filters or closed heat exchangers be used.