IV - 145
Appendix 7. Explanation of Alarms
Appendix 7.10 Multi CPU Errors (A)
A01 MULTI CPU ERROR 4231
Details
- The number of IX and IXEND instructions is not equal.
Remedy
- Read the common information of the error using a programming tool, check error step
corresponding to its numerical value (program error location), and correct the problem.
A01 MULTI CPU ERROR 4350
Details
An incorrect CPU module was designated by the exclusive instruction for multi-CPUs high-
speed communication set in the program.
- The designated module has already been reserved.
- The designated module has not been mounted.
- 'Head I/O No. of target CPU module divided by 16' (n1) is not within 3E0H to 3E3H.
- The designated CPU module cannot execute the instruction.
- The instruction was executed in the single CPU system.
- The designated module is the host CPU module.
Remedy
- Read the common information of the error using a programming tool, check error step
corresponding to its numerical value (program error location), and correct the problem.
A01 MULTI CPU ERROR 4351
Details
The designated CPU module cannot execute the exclusive instruction for multi-CPUs high-
speed communication set in the program.
- The instruction name is not correct.
- The designated instruction is not supported by the CPU module.
Remedy
- Read the common information of the error using a programming tool, check error step
corresponding to its numerical value (program error location), and correct the problem.
A01 MULTI CPU ERROR 4352
Details
- An incorrect number of devices were designated with the exclusive instruction for multi-
CPUs high-speed communication set in the program.
Remedy
- Read the common information of the error using a programming tool, check error step
corresponding to its numerical value (program error location), and correct the problem.
A01 MULTI CPU ERROR 4353
Details
- An unusable device was designated with the exclusive instruction for multi-CPUs high-
speed communication set in the program.
Remedy
- Read the common information of the error using a programming tool, check error step
corresponding to its numerical value (program error location), and correct the problem.