To set the communication type, use the following program.
Data length 7-bit
Parity Even
Stop bit 1-bit
Baud rate 9600 bps
Protocol Non-protocol
Header Not provided
Terminator Not provided
Control line Modem mode
M8002
FNC 12
MOV
H0C86 D8120
D8120 = [ 0000 1100 1000 0110 ]
b15 b0
0C86